TL;DR AI

Key summary

2 min read
  1. At a solar farm, an EKO MS-80S pyranometer on RS485/Modbus RTU worked at first but then kept timing out every 1–2 hours.

  2. Swapping the sensor and cable did not help; the real issue was EMI from a nearby 1000V DC line and power equipment coupling noise into the signal entry.

  3. The RS485 transceiver may have latched up until the connector was reset, pointing to a severe real-world noise problem despite shielded twisted-pair cabling.

  4. The system was eventually converted to 4-20mA, which proved more reliable in the high-voltage environment.